If aluminum alloy cable wants to occupy a place in power engineering and break the monopoly position of copper cable in the cable industry, it should have its unique technical and economic advantages compared with copper cable.
The main parameters of aluminum alloy cable
Aluminum alloy conductor is mainly composed of aluminum. By adding copper (Cu), manganese (Mn), magnesium (Mg), titanium (Ti), chromium (Cr), zinc (Zn), iron (Fe), silicon (Si) and other elements, through advanced synthesis and annealing technology, the shortcomings of pure aluminum cable are made up, and the physical and technological properties of pure aluminum cable are improved. The corrosion resistance and creep resistance of the cable are improved, and the connection stability of the cable is guaranteed even in the case of overload and overheating for a long time. Parameters of aluminum alloy cable are as follows:
(1) Resistivity
The resistivity of aluminum alloy conductor is similar to that of aluminum, about 1.68 times that of copper. Due to the low resistivity of copper cable, the voltage drop of copper cable is small in the case of the same section. But generally in engineering applications, aluminum alloy cable in order to achieve the same carrying capacity, enlarged section, the voltage drop is similar.
(2) Weight
Copper has a density of about 8.9t/m3, while aluminum alloy has a similar density of about 2.7t/m3, which means that under weight per unit area, copper is about 3.3 times heavier than aluminum alloy.
(3) conductivity
Since the conductivity of the conductor is proportional to the cross-section of the conductor, then (8.9/2.7) × (0.612/1) =2, that is, the conductivity of 2kg copper is equivalent to that of 1kg aluminum alloy. In addition, considering the density, when the cross-sectional area of the alloy cable is about 1.5 times that of the copper cable, the electrical performance is the same. Therefore, in the actual cable selection, the section of aluminum alloy cable is about 1.5 times that of copper cable, and the weight is about half that of copper cable.
(4) short-circuit thermal stability
According to "Code for Design of Electric Power Engineering Cable" GB50217-2007, the formula for calculating the allowable small cross section of cable conductor according to the thermal stability condition of short circuit is as follows:
After calculation (this paper omitted the calculation process), can be obtained, copper cable thermal stability coefficient C copper =13700, aluminum alloy cable thermal stability coefficient C aluminum =9000, through the same short circuit current, and short circuit duration is equal to the case, set S copper ≥S base, then S aluminum ≥1.52S base, that is, under the same conditions, The section of aluminum alloy cable must be 1.52 times or higher than that of copper cable.
To sum up, when selecting aluminum alloy cable, the section should be enlarged. When putting about 1.5 times, the main parameters are basically equivalent to that of copper cable.